Air-to-Air Heat Exchanger
Use this kit to asses the heat transfer of a rotary wheel air-to-air heat exchanger.
- Use up to three (3) MX1101 temperature loggers to measure the supply, return and exhaust air temperatures and relative humidity of the air handling system.
- Use one (1) MX2301 weatherproof logger to measure outdoor air temperature.
- To measure the supply and return air flow rate use one (1) hot wire anemometer to conduct a full duct traverse.
- Use up to two (2) Energy Loggers to measure the power draw of the supply and return/exhaust fan motors.
See related documents and content below for how to setup and install the equipment in this kit.
We are available to support NYC Agency Personnel at different project stages. If you are interested in getting additional support contact us.