Hot Water Supply Temperature Reset
Understand how the hot water supply temperature reset works. Explore the sequence of operation (SOO) logic, potential interaction with other SOOs, and additional resources.
Overview
On warmer days during the heating season, the temperature of the water in the hot water heating (HWH) boiler can be lowered (i.e., reset) to meet the more moderate heating demands. The types of boilers covered in this guide include single and staged fixed firing rate boilers and modulating boilers. The assessment approach is suitable for both condensing and non-condensing boilers.
The goal of the HWH boiler temperature reset is to reduce energy consumption in a HWH plant by lowering the supply water temperature when OAT increases. Lowering the supply water temperature decreases boiler cycling and reduces overall boiler runtime.
Basic Control Logic
SOOs are feedback loops that use a combination of sensors, controllers, and actuators to impact a process and maintain a desired state. For example, a thermostat provides a signal to a controller, and the controller sends a signal to the furnace. When the temperature falls below a certain setpoint, the controller sends a signal to the furnace to fire up and to turn on the air handler to provide heated air to the conditioned space. Once the temperature reaches the desired setpoint, the controller sends a signal to reduce the fan speed and/or to turn off the furnace.
Figure 1 presents a schematic of the general principle of the HWH temperature reset feedback loop. HWH supply temperature is modulated based on outdoor air temperature (OAT). As OAT decreases, the HWH temperature is raised and as OAT increases, the HWH temperature is lowered; a water temperature sensor provides the feedback signal needed for this process. The measured error is the difference between the desired temperature setpoint at a given OAT and the actual water temperature. If the measurement error is above a certain threshold, the building automation system (BAS) sends a signal to the boiler to start the firing sequence.

Algorithm for the Sequence of Operation
As seen in Figure 2, supply water temperature varies as a function of OAT. The slope of the curve is called the temperature reset ratio. The minimum temperature of the supply water temperature is a function of the type of boiler being used. A non-condensing boiler must be kept above a supply water temperature so that the byproducts of combustion do not condense in the flue (which creates acidic condensate that can cause corrosion in the flue and boiler), while minimum temperatures can be lower in condensing boilers.

The temperature reset ratio depends on the terminal units being supplied by the boiler. Generally, a reset ratio of 1:1 is used for most traditional radiators, baseboard fin tube radiation, and coils in air handling units. The ratio may be fine-tuned during commissioning to account for other factors in the heating load, such as the distribution piping, envelope, and number of zones.
Notably, the maximum water temperature reset range is bounded at the terminal units to prevent burning occupants. Where devices are protected by a housing such as heating coils, radiators, or fin tube baseboard, maximum supply temperatures can reach 200°F or more. Terminal devices that rely on radiant heat transfer, rather than conduction or convection, generally operate at lower temperatures. Minimum and maximum supply water temperatures must be coordinated with the overall heating output of all terminal devices.
While water temperature reset may be implemented on any boiler, the mode of operation differs:
Fixed firing rate vs. modulating firing rate boilers – A fixed firing rate boiler inherently runs with fewer cycles as the hot water temperature needed in the building is lowered. While inefficiencies in starting and stopping the firing cycles are not reduced, standby losses in the distribution system will be decreased. A modulating firing rate boiler will achieve greater efficiency with water temperature reset. The burner output will be modulated to generate less heat, which leads to longer cycling times; as a result, start and stop inefficiencies are reduced, as are standby losses.
Condensing vs. non-condensing boilers – A boiler that is designed to condense flue gasses should maintain a return water temperature below 140°F. A non-condensing boiler needs to maintain return water temperatures generally above 140°F to prevent flue gasses from condensing and to minimize the risk of corrosion in the flue or boiler heat exchanger. The water temperature reset must be set to maintain the appropriate return water temperature in either case.
How do I…
Assess SOO Energy Usage
Hydronic heating systems meet the heating load of the building by managing the firing of the boiler and controlling the flow and temperature of water through the distribution system. Fuel consumption is generally proportional to the heating load, after accounting for efficiency losses in the system. The type and condition of the boiler, as well as the way in which it is operated, affect system efficiency. While the draft air fan and circulation pumps consume electrical energy, they are considered insignificant compared to the fuel consumption and are not considered in this measurement approach.
Quantify Boiler Fuel Usage (Btu)
Determine the total amount of fuel used by the boiler to heat the water.
Equipment to Measure
What to Measure:
- Average hourly fuel usage of the boiler (gal/h for fuel oil or propane, ccf/h for natural gas).
- Average hourly outdoor air temperature (°F).
Measurement Locations

Calculation Methodology
The general methodology for calculating the total energy consumption of the hot water boiler is to measure the energy consumed by the boiler to generate hot water and the electricity used to run the burner fan motor. These values are summed and regressed against outdoor air temperature to develop a temperature-dependent regression model. Depending on the variability of operations, daily or weekly models may be developed to better characterize the system. This model is then used with climate normal year data to estimate the typical energy use of the system.
Quantify Boiler Electricity Usage (kWh)
Determine the total amount of electricity used to operate the burner fan motors on the boilers.
Equipment to Measure
What to Measure:
- Average hourly current rating (amps) of the burner fan motor.
- Average spot measurements of voltage (V), and power factor of the burner fan motor.
Measurement Locations

Calculation Methodology
The general methodology for calculating the total energy consumption of the hot water boiler is to measure the energy consumed by the boiler to generate hot water and the electricity used to run the burner fan motor. These values are summed and regressed against outdoor air temperature to develop a temperature-dependent regression model. Depending on the variability of operations, daily or weekly models may be developed to better characterize the system. This model is then used with climate normal year data to estimate the typical energy use of the system.
Further Reading
ASHRAE. (2012). Guideline 14 Measurement of Energy, Demand, and Water Savings. ASHRAE
Cleaver Brooks. (2012). Hawk 4000 Boiler Control Manual.
Watts, “Tekmar Glossary – Boiler Outdoor Reset”, Tekmar Control Systems.
Caleffi Hydronic Solutions. (2013). Hydronic Fundamentals. Idronics.
Caleffi Hydronic Solutions. (2014). Controlling Hydronic Systems. Idronics.
Caleffi Hydronic Solutions. (2019). Lowering Water Temperature in Existing Hydronic Heating Systems. Idronics.
Heat-Timer Corp. (2020). What Is Outdoor Reset?