Demand-Controlled Ventilation

Understand how demand control ventilation works. Explore the sequence of operation (SOO) logic, potential interaction with other SOOs, and additional resources.

Overview

Demand-controlled ventilation (DCV) in an air handling unit (AHU) varies the amount of outdoor air (OA) introduced in a space for ventilation purposes based on the carbon dioxide (CO2) level in the space.

The goal of DCV is to save energy by reducing the amount of outdoor air (OA) entering an AHU when the zone is not at full occupancy. Because OA typically needs to be conditioned to meet occupant comfort needs, minimizing OA also minimizes the thermal energy needed to condition the air. Electricity consumption associated with the fan motors can also be reduced if two-speed motors or variable frequency drives (VFDs) are installed.

Basic Control Logic

Figure 1 shows the DCV control logic. The lower left control loop determines supply air temperature (SAT) and air flow leaving the AHU, while the upper right loop feeds zone temperature and CO2 data back to the building automation system (BAS). The BAS, in turn, sets the outdoor air damper (OAD) positions, fans, coil valve positions, zone dampers, and reheat coils to meet the zone temperature and CO2 setpoints.

Diagram of demand control ventilation control logic
Basic DCV control logic.

Algorithm for the Sequence of Operation

The control of the damper position depends on the type of AHU and its associated ventilation strategy. The OA damper (OAD) position is set so that the AHU supplies the required amount of OA to the space. Table 403.3 of the NYC Mechanical Code specifies OA volumes for ventilation based on zone size and on the occupant count of the zone. The DCV algorithm designed to meet the ventilation requirement differs slightly across the three different DCV implementation strategies.

  1. Constant speed fan motors maintain the airflow at a constant rate through the AHU. The OA damper is modulated based on CO2 level in the space.
  2. A two-speed motor provides a low- and high-speed airflow through the AHU. OAD position, fan speed, and coil valve position are operated in response to a combination of the CO2 levels in the space and the heating or cooling load. The fan can operate at high or low speed to maintain a desired discharge air temperature with variable OAD positions.
  3. With variable airflow, the OAD position is controlled in conjunction with the airflow to meet heating/cooling needs, as well as to meet the OA volume requirements. A minimum airflow may be required to maintain proper air mixing in the occupied space for heating or cooling.

Interaction with other SOOs

DCV can interact with airside economizing. DCV energy consumption should only be evaluated when economizing is not occurring.

How do I…

Assess SOO Energy Usage

The AHU also consumes electrical energy to drive the supply and return fans. The on/off scheduling of the fan motors, speed modulation through VFDs (if present), and the system pressure will impact the energy consumption. The type of DCV strategy implemented (constant volume, two speed, or variable volume) will have a direct impact on the electrical consumption of the fan motor.

Quantify Electricity Usage (kWh)

Determine the total amount of electricity used to operate the supply and return fan motors.

Equipment to Measure
mode_fan

What to Measure:

  • Average hourly electricity usage (kWh) of the supply and return fan motors.
  • Average hourly outdoor air temperature (°F), if VFD is temperature dependent.
Learn Morechevron_right
Measurement Locations
Diagram of an air handling unit indicating measurement points.
Location of measurements needed to quantify the electricity usage of the AHU fan motors with demand controlled ventilation
Calculation Methodology

One underlying assumption regarding this SOO is that the heating and cooling loads for the zones being served do not change during the pre- and post-retrofit periods and are correlated to outdoor air temperature (OAT) and hours of operation. It is also assumed that the hourly change in occupancy, and therefore the hourly change in CO2 levels, is reasonably consistent. The sensible and latent energy associated with heating and cooling the outdoor air (OA) and the electricity used by the fan motors is summed by OAT and coincident operating hours, and a regression model is developed. This is used with climate normal year data to develop an estimate of annual heating, cooling, and fan motor electricity consumption.

Assess SOO Performance

DCV affects the amount of heating and cooling energy needed to condition OA air throughout the year. The total energy embodied in the OA entering the system is equal to the latent heat carried by the moisture in the air plus the sensible heat as measured by the dry bulb temperature. The cooling coils remove latent heat through dehumidification. During heating season, it is assumed that only sensible heat is added by the heating coils and changes in latent heat are ignored. DCV reduces the amount of OA that needs to be conditioned based on the CO2 level in the zone served. When the CO2 sensor shows a lower level of CO2 in the space, the DCV control reduces the amount of OA mixed with the return air.

Quantify Heat Transfer Across Heating Coil (Btu)

Determine the total amount of sensible heat added to the supply air by the heating coil.

Equipment to Measure

What to Measure:

  • Average hourly airflow rate (cfm) of discharge air.
  • Average hourly temperature (°F) of discharge, mixed, return, and outdoor air.
Learn Morechevron_right
Measurement Locations
Diagram of an air handling unit indicating measurement points.
Measurements needed to quantify the amount of heating provided by an AHU with demand controlled ventilation.
Quantify Heat Transfer Across Cooling Coil (Btu)

Determine the total amount of sensible and latent heat removed from the supply air by the cooling coil.

Equipment to Measure

What to Measure:

  • Average hourly airflow rate (cfm) of discharge air.
  • Average hourly temperature (°F) of discharge, mixed, return, and outdoor air.
  • Average hourly relative humidity (%) of discharge, mixed, return and outdoor air.
Learn Morechevron_right
Measurement Locations
Diagram of an air handling unit indicating measurement points.
Measurements needed to quantify the amount of cooling provided by an AHU with demand controlled ventilation.

Further Reading

ASHRAE (2018). ASHRAE Guideline 36-2018, High Performance Sequences of Operation for HVAC Systems. Atlanta, GA: ASHRAE. 

Bhatia, A. (2020). “HVAC – Guide to Demand Control Ventilation.” CED Engineering, Course No: M04-037.

Carrier (2001). “Demand Controlled Ventilation System Design.” Doc. No. 811-10088.

Minnesota Department of Commerce, Division of Energy Resources (2015). “Energy Savings from Implementing and Commissioning Demand Control Ventilation.” COMM-20130501-72625.

Trane (2005). “CO2-Based Demand-Controlled Ventilation with ASHRAE Standard 62.1-2004.” Trane Engineers Newsletter, Vol. 34-5.

Section 403.3 of the NYC Mechanical Code

Section C403.7.1 of the NYC Energy Conservation Code