Condenser Water Supply Temperature Reset

Understand how the condenser water supply temperature reset works. Explore the sequence of operation (SOO) logic, potential interaction with other SOOs, and additional resources.

Overview

During periods of milder outdoor air temperatures (OAT) during the cooling season, the condenser water supply temperature (CWST) can be modulated (i.e., reset) in a central cooling plant based on the outside wet bulb temperature (WBT). At low WBT, the condenser water temperature is lowered to reduce the energy required to generate chilled water for the facility.

The goal of CWST reset is to lower the water temperature entering the condenser when the wet bulb temperature is moderate, typically below 70°F (PNNL, 2012). The lower CWST reduces the compressor lift, which reduces the compressor motor power demand. Compressor or chiller lift is the temperature difference between chilled water supply temperature (ChWST) and condenser water return temperature (CWRT). While compressor motor energy consumption is reduced, the cooling tower fan motors must work harder to bring the CWST down. The compressor motor is the dominant energy-consuming component in a chilled water plant, so the overall effect is a reduction in electricity consumption.

info Code Requirement
CWST reset is not required by either the NYC Energy Conservation Code or ASHRAE 90.1, though it may be employed to improve system performance and as part of the ASHRAE 90.1 Energy Cost Budget Method (see Table 11.5.2-1, footnote e).

Basic Control Logic

Sequence of Operations (SOOs) are feedback loops that employ a combination of sensors, controllers, and actuators to impact a process and maintain a desired state. For example, a thermostat provides a signal to a controller, and the controller sends a signal to the furnace. When the temperature falls below a certain setpoint, the controller sends a signal to the furnace to fire up and to turn on the air handler to provide heated air to the conditioned space. Once the temperature reaches the desired set point, the controller sends a signal to reduce the fan speed and/or to turn off the furnace.

Figure 1 is a schematic of the general principle of the CWST reset control feedback loop. If the WBT is moderate and, accordingly, so is the cooling load, then the building automation system (BAS) lowers the CWST setpoint. The CWST temperature sensor provides a feedback signal. In accordance with the measured error, the BAS modulates the speeds of individual cooling tower fans and sequences the tower cells to meet the CWST setpoint.

Diagram of condenser water supply temperature reset control logic
Fundamental CWST reset control logic.

Algorithm for the Sequence of Operation

The general CWST reset algorithm is described in the ASHRAE Handbook, “2019 ASHRAE HVAC – Applications”. Figure 2 depicts a typical application of the algorithm; above 70°F WBT, the CWST setpoint is fixed at 80°F. The cooling tower fans are modulated to maintain the setpoint temperature. Between 60°F and 70°F WBT, fan speeds are set to maintain a CWST that is 10°F greater than the WBT. Below 60°F WBT, the CWST setpoint is fixed at 70°F, which reflects the typical minimum operating CWST for the chiller.

Chart of outdoor air wet-bulb temperature vs condensing loop set point temperature
(Source: Pacific Northwest National Laboratory. (2012). Energy Savings Modeling of Standard Commercial Building Re-tuning Measures: Large Office Buildings PNNL- 21569). Prepared for U.S. Department of Energy.

Figure 2 applies to cooling towers with continuously variable speed fans, which operate at the same speed. If the fans are at two-speed or constant speed, then the cooling tower units are staged. The curve would appear with steps between the minimum and maximum, rather than with a constant slope.

Interaction with other SOOs

CWST reset has potential interactivity with the entire water-cooled chilled water plant.

Supply Air Temperature Reset, Chilled Water Temperature Reset & Differential Pressure Reset – These three SOOs reduce the cooling load that must be met by the chiller system. They are all implemented when OAT is moderate, typically between 60°F to 80°F, which frequently corresponds with the wet bulb temperature range when CWST reset is engaged. As a result, these SOOs work synergistically with CWST reset to meet the cooling demand with less energy. The resulting chiller lift is less, which lowers the condenser water return temperature, which lowers the cooling tower temperature range. With a lower range, the cooling tower fans and compressor both end up working less to meet the CWST setpoint.

Nighttime Zone Temperature Setbacks – Similar to the above strategy, this SOO also reduces the cooling load. Since it occurs only at night, when WBT tends to be lower, CWST may be at its minimum value. To better model annual energy consumption, it is important to model daytime operating conditions separately from nighttime operating conditions.

Waterside Economizing – Waterside economizing runs when OAT is below 55°F, which means it only occurs when the CWST setpoint is at its minimum value. Since the chiller system is turned off or running at part-load, and cooling tower fan speeds are controlled to maintain the desired entering and exiting heat exchanger temperatures, it preempts the CWST reset.

How do I…

Assess SOO Energy Usage

The energy consumption associated with a CWST reset SOO is the electricity used by the chiller, cooling towers and condenser water pumps.

Quantify Electricity Usage (kWh)

Determine the total amount of electricity used to operate the water pump motors, chiller compressor motors, and cooling tower fan motors.

Equipment to Measure

What to Measure:

  • Average hourly electricity usage (kWh) of the chiller.
  • Average hourly outdoor air temperature (°F) and relative humidity (%).
Learn Morechevron_right

What to Measure:

  • Average hourly electricity usage (kWh) of the condenser water pumps.
Learn Morechevron_right

What to Measure:

  • Average hourly electricity usage (kWh) of the cooling towers.
Learn Morechevron_right
Measurement Locations
Diagram of an chilled chilled water plant indicating measurement points.
Location of measurements needed to quantify the energy consumption of a chilled water plant with condenser water supply temperature reset.
Calculation Methodology

The general methodology for calculating the total energy consumption of a water-cooled chilled water plant with CWST reset is to measure the energy consumed by the chiller and condenser water systems at varying outdoor WBTs. These values are summed up and regressed against WBT to develop a temperature-dependent regression model. Depending on the variability of operations, daily, or weekly models may be developed to better characterize the system. This model is then used with climate normal year data to estimate the typical energy use of the chiller and condenser water systems.

Further Reading

ASHRAE. (2018). Guideline 36-2018, High Performance Sequences of Operation for HVAC Systems. ASHRAE.

ASHRAE. (2019). ASHRAE Handbook: HVAC Applications. ASHRAE. Retrieved from https://www.ashrae.org

Fernandez, N. et al. (2012). Energy Savings Modeling of Standard Commercial Building Re-tuning Measures: Large Office Buildings. PNNL-21569.

Taylor, S. (2012). Optimizing Design and Control of Chilled Water Plants. ASHRAE Journal.

Hamilton, G. (2017). Optimizing Hospital Chiller Plants. ES Engineered Systems. https://www.esmagazine.com/articles/98387-optimizing-hospital-chiller-plants.

Hydeman, M., Zhou, G. (2007). Optimizing Chilled Water Plant Control. ASHRAE Journal, Vol. 49.

Knox, J.A., Nevius, D.S., Knox, P.N. (2017). Two simple and accurate approximations for wet-bulb temperature in moist conditions, with forecasting applications. Bulletin of the American Meteorological Society, Vol. 98, Issue 9; pp. 1897-1906.

Lawrence Berkeley National Laboratory (2009). Energy Design Resources. Chilled Water Plant Design Guide. https://datacenters.lbl.gov/sites/default/files/EDR_DesignGuidelines_CoolToolsChilledWater.pdf.