Airside Economizing

Understand how airside economizing works. Explore the sequence of operation (SOO) logic, potential interaction with other SOOs, and additional resources.

Overview

Airside economizing saves energy by using outdoor air to cool a facility instead of the chilled water plant, or direct expansion cooling in an air handling unit (AHU), when the outdoor air temperature (OAT) meets certain criteria, as described in the NYC Energy Conservation Code (Table C403.5.3.3).

Basic Control Logic

Sequences of operation (SOOs) are essentially feedback loops that employ a combination of sensors, controllers, and actuators to impact a process and maintain a desired state. For example, a thermostat provides a signal to a controller, and the controller sends a signal to the furnace. When the temperature falls below a certain setpoint, the controller sends a signal to the furnace to fire up and to turn on the air handler to provide heated air to the conditioned space. Once the temperature reaches the desired setpoint, the controller sends a signal to reduce the fan speed and/or to turn off the furnace.

Figure 1 presents a schematic of the general principle of the economizing control feedback loop. If OAT is within the economizing range, the outdoor air damper (OAD) position is opened 100%. The control signals to the AHU are adjusted to consider that the OAD is 100% open while still meeting the zone temperature setpoints.

Diagram of airside economizing reset control logic
Fundamental airside economizing control logic.

The goal of economizing is to use less energy to meet the cooling load. The AHU draws in outdoor air when the outdoor air temperature and humidity are in a range to allow it to cool interior spaces. Optimizing the amount of outdoor air reduces the amount of energy needed to condition the space.

ASHRAE Standard 90.1-2019 and NYC code requires that outdoor air be introduced when conditions are warranted. This SOO is suitable for all AHUs with variable OAD position control, including constant air volume, two-speed air volume, and variable volume AHUs. Control strategies may be based on dry bulb temperature or enthalpy.

Algorithm for the Sequence of Operation

Economizing is generally implemented using three methods:

Dry Bulb Temperature

The OAD position opens when the dry bulb temperature is within a suitable range. In NYC, the maximum temperature at which the energy code allows for economizing is 65°F. As OAT approaches the discharge air temperature (DAT), the damper position is modulated, and the cooling coil is turned off (modulated economizer mode). At the higher end of this range, the OAD position is 100% and the cooling coil is modulated to provide sufficient cooling and dehumidification (integrated economizer mode). Dry bulb is the simplest economizer control method.

Dry Bulb Temperature Difference

The OAD position opens when the dry bulb temperature of the return air is higher than the dry bulb temperature of the outdoor air. As OAT approaches DAT, the damper position is modulated, and the cooling coil is turned off (modulated economizer mode). At the higher end of this range, the OAD position is 100% and the cooling coil is modulated to provide sufficient cooling and dehumidification (integrated economizer mode).

Enthalpy

There are two methods of enthalpy economizing:

  1. Single Enthalpy – This control method takes humidity into account by measuring the enthalpy of air instead of dry bulb temperature; economizing is used only below 28 Btu/lb. When humidity is high, reducing the outdoor air fraction lowers the cooling coil demand, as less moisture needs to be removed by condensing it on the coil.

  2. Dual Enthalpy – Dual enthalpy control turns off economizing when outdoor air enthalpy is greater than return air enthalpy.

info Enthalpy Control Sensors
Enthalpy control requires expensive, high-quality sensors. Use of low quality sensors are prone to error and may not lead to proper execution of the SOO and yield lower than intended energy savings.

Interaction with other SOOs

Airside economizing can interact with demand-controlled ventilation, in that the airside economizing will inherently over ventilate a space but is doing so with no chilled water.

How do I…

Assess SOO Energy Usage

The AHU consumes electrical energy to drive the supply and return fans. The on/off scheduling of the fan motors, speed modulation through VFDs (if present), and the system pressure will impact the energy consumption. Economizing only modulates the volume of outdoor air introduced to the AHU. Unless the fan motor is changed or a VFD is installed as a part of the retrofit, it is assumed that fan speed and power do not change between the pre- and post-retrofit conditions.

Quantify Electricity Usage (kWh)

Determine the total amount of electricity used to operate the supply and return fan motors.

Equipment to Measure
mode_fan

What to Measure:

  • Average hourly electricity usage (kWh) of supply and return fan motors.
  • Average hourly outdoor air temperature (°F) and relative humidity (%).
Learn Morechevron_right
Measurement Locations
Diagram of air handler unit indicating measurement points.
Location of measurements needed to quantify the energy consumption of an AHU with economizing.
Calculation Methodology

One underlying assumption regarding this SOO is that the heating and cooling loads for the zones being served do not change during the pre- and post-retrofit periods and are correlated to OAT and hours of operation. The sensible and latent energy associated with cooling the air is summed by OAT and coincident operating hours, and a regression model is developed. This is used with climate normal year data to develop an estimate of annual cooling consumption.

Assess SOO Performance

Economizing only affects the cooling energy consumption needed to condition the outdoor air and is not used during heating season. The total energy embodied in the outdoor air entering the system is equal to the latent heat carried by the moisture in the air plus the sensible heat as measured by the dry bulb temperature. The cooling coils remove latent heat through dehumidification. When the dry bulb temperature or enthalpy is in the economizing range, the OAD opens and the cooling coil valve is modulated or turned off. Therefore, to evaluate the benefit of economizing, it is only necessary to calculate the change in energy removed from outdoor air when conditions warrant economizing.

Quantify AHU Cooling Load (Btu)

Determine the operating characteristics of the air handling unit.

Equipment to Measure

What to Measure:

  • Hourly outdoor air damper position (%) (from BAS).
  • Hourly return air damper position (%) (from BAS).
  • Average hourly supply air flow rate (CFM).
  • Average hourly temperature (°F) of discharge, mixed, return and outdoor air.
  • Average hourly relative humidity (%) of discharge, mixed, return and outdoor air.
Learn Morechevron_right
Measurement Locations
Diagram of air handler unit indicating measurement points.
Measurements needed to quantify the amount of cooling provided by an AHU with economizing.

Further Reading

ASHRAE. (2019). ASHRAE Standard 90.1-2019: Energy Standard for Buildings Except Low-Rise Residential Buildings. Atlanta, GA: ASHRAE.

New York City Department of Buildings. (2020). New York City Energy Conservation Code (NYCECC). Retrieved 2021, from Section C403.5.3.3: https://up.codes/viewer/new_york_city/nyc-energy-conservation-code-2020/chapter/C4/commercial-energy-efficiency#C403.5.3.3