Lighting Fixture System
Understand how the lighting fixture system works. Explore component overviews, measurements, and additional resources.
Overview
A lighting fixture system produces light to illuminate a specific area or areas. Current is received from the electrical distribution system. The group of fixtures that comprise a lighting system can be configured in many ways with different lamp types. A building can have one or more lighting fixture systems. The main components of an individual lighting fixture are lamps, ballasts, and controls.


Components
Lamps
Lamps refer to the enclosure of the lighting source. The most common types of lamps are incandescent, fluorescent, high intensity discharge (HID), induction and LED. Many types of lamps can be used within a facility. Lamps convert electrical energy to light, and a portion to heat. The efficiency of the lamp in minimizing losses to heat is the biggest determining factor in the energy efficiency of the lighting fixture system.
Ballast
The ballast is an electrical device that regulates the voltage and current supplied to a lamp. All lamp types, other than incandescent, need ballasts to ensure stable operation. Ballasts come in various types, each designed for specific lamps, and some fixture systems have ballasts integrated into the lamp component. The regulation of voltage and current results in some energy loss as heat, and ballast efficiency varies depending on how well these losses are minimized.
Housing
The fixture housing is the physical receptacle that houses the lamp and ballast. The housing may include shutters or diffusers which direct and disperse the light. Some housing is designed to disperse the heat generated by the lamp and ballast more effectively, which increases the life of the fixture.
Controls
Controls regulate the operation of the light fixtures, such as when they are turned on and off, and their brightness. Controls can be manual or automatic. Manual controls are wall switches within a space and circuit breakers at the electrical panelboard and switchgear. Automatic controls use sensors and/or timers to determine when and how to regulate the fixture operation. Some automatic controls have their own control panel wired directly to the circuits at the lighting panelboards or the ballasts of individual fixtures.
How do I…
Quantify System Electricity Usage (kWh)
The power draw of each unit is typically consistent enough that only a portion of the fixtures need to be measured in order to estimate the consumption of the entire plant. Fixtures should be grouped by model for power measurements, and group by operating schedule for duration measurements.
Select a strategy depending on what can be measured:
Measure True Power at Main FeedFor a dedicated panelboard.
For a dedicated panelboard.
Measure the average hourly energy (kWh), and spot measurement of true RMS power (kW) at the panelboard. This strategy works when measuring all fixtures served by a panelboard.
How to Measure
Click any measurement below for detailed setup, data collection, and troubleshooting instructions.
Use this technique to measure the average hourly electricity supplied to the light fixture system from the panelboard or switchgear.
Use this technique to take a spot measurement of true RMS power (kW) of a light fixture system from the panelboard or switchgear.
Borrow Equipment and Download Calculator
Reserve loggers, download the calculator, and enter your measured data.
This tool kit includes:
Lighting Fixture Energy Calculator (Energy From Panelboard)
Provides an estimate of the annual electricity consumption of a lighting panel, using kWh measurements at the panelboard.
For more details about the methodology behind this calculator, see Lighting Energy Consumption.
Download CalculatordownloadMeasurement Locations


Measure Current at Circuit Breakers in PanelboardFor mixed panelboard.
For mixed panelboard.
Measure the average hourly current (Amps), spot measurements of voltage (V), power factor, and true RMS power (kW) at the panelboard.
This strategy works when measuring a sample of fixtures in a panelboard, or when the panelboard is mixed and only a group of circuit breakers will be measured.
How to Measure
Click any measurement below for detailed setup, data collection, and troubleshooting instructions.
Use this technique to measure lighting fixture current (Amps) from the panelboard or switchgear at one-hour intervals.
Use this technique to take a spot measurement of voltage (V), power factor, and true RMS power (kW) of a light fixture system from the panelboard or switchgear.
Borrow Equipment and Download Calculator
Reserve loggers, download the calculator, and enter your measured data.
Lighting Fixture Energy (Current) Calculator
Provides an estimate of the annual electricity consumption of a lighting panel, using data from the panelboard's three phases.
For more details about the methodology behind this calculator, see Lighting Energy Consumption.
Download CalculatordownloadMeasurement Locations

Measure Lighting Runtime
Measure the hourly lighting runtime and use the expected fixture wattages (W), number of fixtures, lamps and ballasts.
How to Measure
Click any measurement below for detailed setup, data collection, and troubleshooting instructions.
Use this technique to measure the hours of operation of a light fixture or lamp.
Use this technique to take a spot measurement of true RMS power (kW) of a light fixture at the panelboard.
Borrow Equipment and Download Calculator
Reserve loggers, download the calculator, and enter your measured data.
This tool kit includes:
Lighting Fixture Energy (Runtime) Calculator
Provides an estimate of the annual electricity consumption for a sum of lighting fixtures, using measured runtime data, expected fixture wattages, number of fixtures, lamps and ballasts.
For more details about the methodology behind this calculator, see Lighting Energy Consumption.
Download CalculatordownloadFurther Reading
California Energy Commission (June 2015). 2016 Building Energy Efficiency Standard for Residential and Nonresidential Buildings, Title 24, Part 6, Chapter 6: Residential Compliance Manual, CA: California