Reheats While Cooling Measurement Kit
Typically, simultaneous heating and cooling is not advisable, as it uses extra energy. However, there are some cases where this may be needed. This measure is an example of this case, though it is still advisable to minimize it.
This measure is best used for a AHU/RTU with multiple zones with reheats. It monitors the mixed air (MAT), supply air (SAT) and zone temperatures to check that the SAT is not too low that the reheats are all on. It is important to put the zone temperature loggers closest to the discharge / terminal opening.
- Use two MX1101 Temp/RH loggers for MAT and SAT measurements.
- Use one or more MX1101 Temp/RH loggers per zone.
See related documents and content below for how to setup, install and analyze the data.
Kit Contents
Add all tools in this kit with selected quantities to the cart.
HOBO Temp/RH Logger Onset MX1101
Measures and records temperature and relative humidity. Using bluetooth technology you can transmit your data wirelessly to your mobile device using …
125
Available
maxes[0]) qtys[0] = maxes[0];
" :disabled="maxes[0] === 0" :class="{ 'opacity-40 cursor-not-allowed': maxes[0] === 0 }" class="text-nycet-blue font-bold w-14 text-center border border-gray-300 rounded px-4 py-2 appearance-none [&::-webkit-outer-spin-button]:appearance-none [&::-webkit-inner-spin-button]:appearance-none [-moz-appearance:textfield]">