Minimum Outdoor Air Damper (OAD) Position Check Measurement Kit

A good operating level of ventilation strikes a good balance between indoor air quality (IAQ) and energy efficiency. Under-ventilation compromises air quality, and over-ventilation wastes energy since it requires more heating or cooling energy of outdoor air than is needed.

For buildings that do not have demand controlled ventilation (DCV), there exists a minimum outdoor air damper (OAD) position that should be set such that the maximum CO2 concentration for any served zone reaches the maximum level considered sufficient for good indoor air quality; this is typically 900 ppm, but may be set as high as 1,100 ppm. This measure determines whether the minimum OAD position is selected to capture the right balance between healthy IAQ during maximum load occupancy and energy efficiency.

warning When to Measure
This measure must be done when the air-side economizer is not in use. This typically occurs during the height of heating and cooling seasons, i.e., during extreme temperatures. Otherwise, the additional air that is introduced for free cooling reduces the CO2 concentration. To avoid this situation, you may choose to override / disable air-side economizing while gathering data.

See related documents and content below for how to setup, install and analyze the data.

Kit Contents

Add all tools in this kit with selected quantities to the cart.
CO2/Temp/RH Data Logger Onset MX1102
CO2/Temp/RH Data Logger Onset MX1102
Measures and records carbon dioxide, temperature and relative humidity. Uses bluetooth to transmit data wirelessly to a mobile device using the …
17 Available