Minimum Outdoor Air Damper (OAD) Position Check Measurement Kit
A good operating level of ventilation strikes a good balance between indoor air quality (IAQ) and energy efficiency. Under-ventilation compromises air quality, and over-ventilation wastes energy since it requires more heating or cooling energy of outdoor air than is needed.
For buildings that do not have demand controlled ventilation (DCV), there exists a minimum outdoor air damper (OAD) position that should be set such that the maximum CO2 concentration for any served zone reaches the maximum level considered sufficient for good indoor air quality; this is typically 900 ppm, but may be set as high as 1,100 ppm. This measure determines whether the minimum OAD position is selected to capture the right balance between healthy IAQ during maximum load occupancy and energy efficiency.
- Use one CO2/Temp/RH logger in the return air duct and/or one per zone where high occupant loads are experienced
See related documents and content below for how to setup, install and analyze the data.