Air-Cooled Chiller Measurement Kit
Use this kit to assess the energy consumption (electricity usage) of an air-cooled chiller system.
Take hourly average measurements of electricity (kW, voltage, current, power factor) during the chiller operating season. An energy logger that can measure three-phase power should be used.
- Use only one energy logger per chiller system.
- Use one MX2301 weatherproof data logger to take hourly measurements of the outdoor air dry-bulb temperature.
- Use one thermocuple sensor and logger to take hourly average measurements of the chilled water supply and return temperatures (via pipe surface temperature measurements).
- Use one ultrasonic flow meter to take hourly average chilled water flow measurements.
See related documents and content below for how to setup and install the tools in this kit.
We are available to support NYC Agency Personnel at different project stages. If you are interested in getting additional support contact us.
Kit Contents
Documents
Frequently Asked Questions
Can I use weather data from my BAS?
If you can get hourly trend data of the outdoor air dry-bulb temperature via the BAS, you can use that data in place of measurements with the MX2301 logger.
Do I need to double up this kit if I need to measure more than one chiller?
You can measure one chiller at a time or request an additional ELITEpro data logger, two thermocouples, one utrasonic flow meter per chiller and one HOBO four channel logger for every two chillers.